2. Nominal Tonnage
20
3. Capacity BTU/HR
244,000
4. Voltage
3ph, 460/60
5. EER/SEER2
11/NA
Nominal CFM
8000
Outdoor Fan Diameter in.
6 X 24
Outdoor Fan No. Motors/HP
6 at 1/3 HP
Outdoor Fan Motor RPM
1075
Indoor Fan Diameter in.
2/18x9
Indoor Fan Drive Type
Belt
Indoor Fan Motor HP
5
Indoor Fan Motor RPM
1725
Filter (NO.) Size Recommended in.
(8)2x25x20
1. Pkg. Unit Type
Electric Electric
Refrigerant Charge Oz. Circuit 1/Circuit 2
402/331
Compressor No./Type
2/Scroll
Unit Dimensions Width x Depth x Height
152.1 X 85.9 X 57
Shipping Weight lbs.
2277
Individual Item Weight lbs.
2151
- Factory charged with R-410A HFC refrigerant
- Scroll compressors with internal line break overload and high pressure protection
- Two independent refrigerant circuits each with a scroll compressor provide two stage cooling operation.
- Convertible airflow – vertical down flow or horizontal side flow
- Factory Installed ClearControl™ (DDC) and sensors which can connect to LonWorks™ or BACnet® BAS systems for remote monitoring and control.
- Cooling operation up to 125°F ambient
- High Pressure and Low Pressure/Loss of charge protection standard on all models.
- Single slab, single pass designed evaporator and condenser coils facilitate easy cleaning for maintaining high efficiencies.
- Foil faced insulation encapsulated throughout entire unit minimizes airborne fibers from the air stream.
- Hinged major access door with heavy-duty gasketing, 1/4 turn latches and door retainers.
- Slide Out Indoor fan assembly for added service convenience.
- Single point electrical connections.
- High performance belt drive motor with variable pitch pulleys and quick adjust belt system.
- Condenser motors are internally protected, totally enclosed with shaft down design.
- 24 volt control system with resettable circuit breakers